GTAD 12V200AH
Nominal Voltage |
12V (6 cells per unit) |
Nominal Capacity (10HR) |
200Ah/10.8V |
Terminal Type |
T18 |
Self-discharge (25°C) |
3 months |
Remaining capacity: 91% |
6 months |
Remaining capacity: 82% |
12 months |
Remaining capacity: 65% |
|
Cyclic Charging Voltage (25°C) |
14.60 to 15.00V Temperature compensation : -30mV/°C/Block |
Float Charging Voltage (25°C)
|
13.60 to 13.70V Temperature compensation : -20mV/°C/Block |
Design Life |
10 years for floating (25°C) Eurobat (20°C): 6-9 years, general purpose. |
Internal Resistance (Fully charged, 25°C) |
Approx. 3mΩ |
Operating Temp. Range |
Discharge |
-15°C~50°C (5°F~122°F) |
Charge |
-10°C~50°C (14°F~122°F) |
Storage |
-20°C~50°C (-4°F~122°F) |
|
Dimensions (LxWxH) |
Length |
522±2mm |
Width |
238±2mm |
Height |
218±2mm |
Total height |
222±2mm |
|
Weight |
62.0kg±3% |
Applications
- Uninterruptable Power Supply (UPS)
- Electric Power System (EPS)
- Emergency backup power supply
- Alarm and security system
- Electronic apparatus and equipment
- Communication power supply
- Solar Power System
รีวิว